Availability: | |
---|---|
Quantity: | |
Product Feature
Product Introduction
The nonlinear currents generated by the massive use of modern power and electric equipment are impacting the power grid and aggravate its pollution in the harmonic form, cause overload failures to capacitors, transformers and transmission devices and generate serious interference to measuring, transmitting and calculating devices; in addition, resonance and voltage distortions may also result in power supply accidents. Series reactors could effectively improve or avoid such problems. After installing the capacitor and reactor in series, the resonance frequency is lower than the minimum of the system (usually 5th and 7th waves), so that compatibility is showed under power frequency and power factor is improved; meanwhile, there is no need to worry about the amplification of harmonic wave. With satisfactory impedance matching, the capacitor bank could absorb 30% to 60% of the harmonic currents (5th harmonic wave, for example).
Applicable Standards
IEC289:1987 Reactor
GB10229-88 Reactor(eqvIEC289:1987)
JB9644-1999 Reactor used for semiconductor electrical driving
Product Selection
Technical Specifications
Operating frequency: | 50Hz-60Hz |
Rated operating current: | 5A-2000A |
Rated operating voltage: | 220V-10KV |
Temperature rise: | ≤95K |
Noise: | ≤65dB |
Three-phase equilibrium degree: | -5%…+5% |
Reactive Strength: | core-winding3000VAC/50Hz/5mA/10s free of arcing breakage(ftested in factory) |
Insulation Resistance: | 1000VDC,insulation resistance≥100MΩ |
Degree of protection: | IP00-IP20 |
Reduction factor: | 5,67%,7%,14% |
Pn Performance range Pn: | 5Kvar…100kvar |
Monitoring: | temperature switch is integrated,contacts are fitted on terminals. |
Temperature classes: | ta40℃/F,H |
Installation altitude: | ≤2000m above sea level |
Storage temperature: | -25℃…+55℃ |
Transport temperature: | -25℃…+70℃ |
Permissible humidity rating: | humidity 5%…95% occasional condensation permissible |
Technical Parameter
Product Size
Choking factor p = 5.67 %, L = constant to 1.82 · Ithmax, fRES = 210 Hz
Order No | Picture NO. | Filter bank capacity QC kvar | Inductance (mH) | Dimensions (L*W*H) | Mounting (D1*W1) | Rated (A) | Connections K = Terminal F = Flat termination | Total weight per (KG) |
ATR002800400SA05.67X | A | 5 | 6.12 | 195*100*210 | 120*72 | 8.0 | K | 3.7 |
ATR004300400SA05.67X | A | 7.5 | 4.081 | 195*100*210 | 120*92 | 12.0 | K | 5 |
ATR005700400SA05.67X | A | 10 | 3.06 | 195*150*165 | 120*92 | 16.0 | K | 6.4 |
ATR007100400SA05.67X | A | 12.5 | 2.45 | 195*165*165 | 120*112 | 20.0 | K | 9.1 |
ATR0085000400SA05.67X | A | 15 | 2.04 | 195*165*165 | 120*112 | 24.0 | K | 9.3 |
ATR011300400SA05.67X | A | 20 | 1.53 | 230*160*185 | 150*95 | 32.0 | K | 13 |
ATR014200400SA05.67B | A | 25 | 1.22 | 250*165*200 | 182*95 | 40.0 | K | 18.3 |
ATR017000400SA05.67B | B | 30 | 1.02 | 250*170*200 | 182*105 | 50.0 | F | 18 |
ATR022700400SA05.67B | B | 40 | 0.77 | 250*180*200 | 182*115 | 65.0 | F | 25.3 |
ATR028400400SA05.67B | B | 50 | 0.61 | 290*185*220 | 214*118 | 80.0 | F | 34.1 |
ATR034000400SA05.67B | B | 60 | 0.51 | 290*200*200 | 214*128 | 95.0 | F | 35.6 |
ATR045400400SA05.67B | B | 80 | 0.38 | 320*205*285 | 243*130 | 130.0 | F | 42 |
ATR051000400SA05.67B | B | 90 | 0.34 | 320*210*310 | 213*135 | 145.0 | F | 47 |
ATR056700400SA05.67B | B | 100 | 0.31 | 320*220*310 | 243*140 | 160.0 | F | 51.9 |
Choking factor p = 7 %, L = constant to 1.66 · Ithmax, fRES = 189 Hz
Order No | Picture NO. | Filter bank capacity QC kvar | Inductance (mH) | Dimensions (L*W*H) | Mounting (D1*W1) | Rated (A) | Connections K = Terminal F = Flat termination | Total weight per (KG) |
ATR003500400SA07X | A | 5 | 7.2 | 195*100*210 | 120*72 | 7.5 | K | 3.3 |
ATR005300400SA07X | A | 7.5 | 5 | 195*100*210 | 120*92 | 11 | K | 4.8 |
ATR007000400SA07X | A | 10 | 3.8 | 195*150*165 | 120*92 | 15 | K | 5.9 |
ATR008800400SA07X | A | 12.5 | 3 | 195*165*165 | 120*112 | 19 | K | 8.6 |
ATR010500400SA07X | A | 15 | 2.5 | 195*165*165 | 120*112 | 23 | K | 8.8 |
ATR014000400SA07X | A | 20 | 1.8 | 230*160*185 | 150*95 | 30 | K | 12.8 |
ATR017500400SA07B | B | 25 | 1.4 | 250*165*200 | 182*95 | 38 | K | 19.1 |
ATR021000400SA07B | B | 30 | 1.2 | 250*170*200 | 182*105 | 45 | F | 19.6 |
ATR028000400SA07B | B | 40 | 0.95 | 250*180*200 | 182*115 | 60 | F | 24.7 |
ATR035000400SA07B | B | 50 | 0.75 | 290*185*220 | 214*118 | 75 | F | 26.5 |
ATR042000400SA07B | B | 60 | 0.62 | 290*200*220 | 214*128 | 90 | F | 34.1 |
ATR056000400SA07B | B | 80 | 0.46 | 320*205*285 | 243*130 | 122 | F | 40 |
ATR063000400SA07B | B | 90 | 0.43 | 320*210*310 | 213*135 | 130 | F | 45 |
ATR070000400SA07B | B | 100 | 0.37 | 320*220*310 | 243*140 | 150 | F | 50 |
Choking factor p = 14 %, L = constant to 1.4 · Ithmax, fRES = 134 Hz
Order No | Picture NO. | bank capacity QC kvar | Inductance | Dimensions (L*W*H) | Mounting (D1*W1) | Rated (A) | Connections K = Terminal F = Flat termination | Total weight per (KG) |
ATR007000400SA14X | A | 5 | 16.6 | 195*120*210 | 120*92 | 7 | K | 5.1 |
ATR010500400SA14X | A | 7.5 | 11.1 | 195*120*210 | 120*112 | 10 | K | 8.1 |
ATR014000400SA14X | A | 10 | 8.29 | 195*120*210 | 120*112 | 14 | K | 9.4 |
ATR017500400SA14X | A | 12.5 | 6.63 | 195*120*210 | 120*112 | 18 | K | 12 |
ATR021000400SA14X | A | 15 | 5.53 | 250*165*200 | 182*95 | 21 | K | 16 |
ATR028000400SA14X | A | 20 | 4.14 | 250*185*200 | 182*115 | 30 | K | 18 |
ATR035000400SA14B | B | 25 | 3.32 | 290*150*210 | 214*113 | 35 | K | 28 |
ATR042000400SA14B | B | 30 | 2.76 | 290*185*220 | 214*118 | 42 | K | 26 |
ATR056000400SA14B | B | 40 | 2.07 | 290*215*280 | 214*118 | 56 | F | 35.2 |
ATR070000400SA14B | B | 50 | 1.66 | 3320*230*275 | 243*135 | 70 | F | 37.2 |
ATR084000400SA14B | B | 60 | 1.38 | 320*230*310 | 243*135 | 85 | F | 51.1 |
ATR112000400SA14B | B | 80 | 1.04 | 375*250*320 | 260*165 | 110 | F | 54 |
ATR126000400SA14B | B | 90 | 0.92 | 375*250*320 | 260*165 | 125 | F | 58 |
ATR140000400SA14B | B | 100 | 0.829 | 375*265*360 | 260*175 | 140 | F | 62 |