| SKU: | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Availability: | |||||||||
| Quantity: | |||||||||
| FC610: Intelligent Backpack Water Pump VFD The FC610 series is a water pump control specialized machine developed by Janson Control, specially designed for small and mediumpower motors in the water pump industry. It has a high protectionrating of IP54, is waterproof and dustproof, simple and compact, withoutstanding performance, easy system operation, intelligent, highlyreliable, made with high quality materials, good quality, and lowmotor noise. It can achieve single pump control and intelligentmulti-pump linkage operation. Stable Pressure, Zero Hassle: With its advanced Built-in PID, the FC610 maintains precise constant pressure, eliminating annoying water pressure fluctuations in buildings and factories. Intelligent Multi-Pump Staging: Manage up to 5 pumps simultaneously. The FC610 intelligently balances the load and rotates pump usage to ensure equal wear and tear, significantly extending your equipment's lifespan. Ultimate Pump Protection: Features specialized safety logic, including Dry-Run Protection and Pipe-Burst Detection, preventing catastrophic pump failures and costly repairs. Energy-Saving Sleep Mode: Automatically enters low-power mode during zero-demand periods, cutting energy costs by up to 30%–50% for residential and commercial users. | |||||||||
FC610
Janson Controls
| Item No. | Adaptable Motor (kW) | Input Current (A) | Output Current (A) | Rate Capacity (kVA) | W (mm) | H (mm) | D (mm) | W1 (mm) | H1 (mm) | GW (kg) |
| 3 Phase Input and 3 Phase Output 380V (-15%~+15% Tolerance) | ||||||||||
| FC610-4T-2.2P | 2.2 | 5.8 | 5.1 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-4.0P | 4 | 10 | 8.6 | 5.9 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-5.5P | 5.5 | 14.6 | 12.5 | 8.6 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-7.5P | 7.5 | 20.5 | 17.5 | 12 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-11P | 11 | 28 | 25 | 16 | 200 | 235 | 146 | 129 | 225 | 4 |
| 1 Phase Input and 3 Phase Output 220V (-15%~+15% Tolerance) | ||||||||||
| FC610-2S-0.75P | 0.75 | 8.2 | 4 | 1.5 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-1.5P | 1.5 | 14 | 7 | 3 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-2.2P | 2.2 | 23 | 9.6 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| Item No. | Adaptable Motor (kW) | Input Current (A) | Output Current (A) | Rate Capacity (kVA) | W (mm) | H (mm) | D (mm) | W1 (mm) | H1 (mm) | GW (kg) |
| 3 Phase Input and 3 Phase Output 380V (-15%~+15% Tolerance) | ||||||||||
| FC610-4T-2.2P | 2.2 | 5.8 | 5.1 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-4.0P | 4 | 10 | 8.6 | 5.9 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-5.5P | 5.5 | 14.6 | 12.5 | 8.6 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-7.5P | 7.5 | 20.5 | 17.5 | 12 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-11P | 11 | 28 | 25 | 16 | 200 | 235 | 146 | 129 | 225 | 4 |
| 1 Phase Input and 3 Phase Output 220V (-15%~+15% Tolerance) | ||||||||||
| FC610-2S-0.75P | 0.75 | 8.2 | 4 | 1.5 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-1.5P | 1.5 | 14 | 7 | 3 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-2.2P | 2.2 | 23 | 9.6 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
1.Intelligent Control for Water Stability
Advanced Constant Pressure Logic: Real-time feedback from pressure sensors ensures the system reacts instantly to demand changes.
Multi-Pump Master/Slave Mode: Supports intelligent staging of up to 5 pumps (VFD + fixed speed combination). Includes automatic rotation to prevent pump seizure from long-term inactivity.
2.Proactive Safety & Durability
Specialized Pump Safeguards: Integrated protection against dry-running, high/low pressure, pipe leakage, and motor overheating.
Grid & Environment Resilience: Tolerates ±15% voltage fluctuations and features a reinforced enclosure to withstand the humidity and heat of tropical pump rooms.
3.Eco-Friendly & Cost-Effective
Smart Sleep/Wake-up: The drive "sleeps" when demand stops and "wakes up" instantly when pressure drops, drastically reducing electricity bills.
Simplified Engineering: Built-in macros for pump applications mean you don't need to be a VFD expert to get the system running perfectly.
4.Connectivity & Remote Monitoring
Dual RS485 Ports: Standard Modbus-RTU communication for easy integration with Building Management Systems (BMS) or remote IoT monitoring apps.
Flexible Interfaces: Easily connect pressure transducers, float switches, and remote emergency stops for a fully automated station.
1.Intelligent Control for Water Stability
Advanced Constant Pressure Logic: Real-time feedback from pressure sensors ensures the system reacts instantly to demand changes.
Multi-Pump Master/Slave Mode: Supports intelligent staging of up to 5 pumps (VFD + fixed speed combination). Includes automatic rotation to prevent pump seizure from long-term inactivity.
2.Proactive Safety & Durability
Specialized Pump Safeguards: Integrated protection against dry-running, high/low pressure, pipe leakage, and motor overheating.
Grid & Environment Resilience: Tolerates ±15% voltage fluctuations and features a reinforced enclosure to withstand the humidity and heat of tropical pump rooms.
3.Eco-Friendly & Cost-Effective
Smart Sleep/Wake-up: The drive "sleeps" when demand stops and "wakes up" instantly when pressure drops, drastically reducing electricity bills.
Simplified Engineering: Built-in macros for pump applications mean you don't need to be a VFD expert to get the system running perfectly.
4.Connectivity & Remote Monitoring
Dual RS485 Ports: Standard Modbus-RTU communication for easy integration with Building Management Systems (BMS) or remote IoT monitoring apps.
Flexible Interfaces: Easily connect pressure transducers, float switches, and remote emergency stops for a fully automated station.
| Electrical Specification | |
| Input Voltage | Single Phase/Three Phase 200-240V, Three Phase 380-440V |
| Fluctuate no more than±10%,Imbalance Rate <3% | |
| Input Frequency | 50/60Hz ± 5% |
| Output Voltage | 0V-Input Voltage |
| 10~60Hz | |
| Performance | |
| Overload Capacity | 110% rated output current for 1 minute |
| Control Method | V/F Control |
| Run Command Setting Method | Operation panel setting, analog setting, communication setting |
| Speed Setting Method | Digital setting, analog setting/pulse setting, communication setting |
| Protective function | |
| Overvoltage Stall | Bus voltage automatic control to prevent overvoltage fault |
| Automatic Current Limiting Protection | Output current is automatically limited to prevent over-current faults |
| Overload Pre-Alarm & Alarm | Overload Pre-warning and protection |
| Output Phase Loss Protection | Output phase loss automatic detection and alarm function |
| Overvoltage & Overflow Stall Control | Automatically limit current and voltage during operation to prevent frequent over-current and over-voltage tripping |
| Output Short-to-Ground Protection | Effective protection function for output short circuit to ground |
| Output Phase-to-Phase Short Circuit Protection | Output interphase short circuit effective protection function |
| Input & Output | |
| External analog power supply | +24V,load capacity 100mA |
| Analog Input | AI1:Voltage 0-10V/0-20mA |
| AI2:Voltage 0-10V/0-20mA | |
| Digital Input | DI1、DI2 |
| Digital Output | DO1 |
| Relay output | TA/TB/TC:Contact rating 250VAC/3A Or 30VDC/1A |
| MUDBUS Communication | A+、B- |
| Operation Display | |
| LED Display | 4 digit LED digital tube |
| Output frequency, output current, current pressure, set pressure and fault code etc. | |
| Indicator Light | 4 status lights |
| Environmental characteristics | |
| Working Temperature | -10-+40℃, Maximum temperature is 50°C, Air Temperature change is less than 0.5°C/min,40-50℃ Derating is required, output current derating 2% for each 1℃ |
| Storage Environment Temperature | -40-+70℃ |
| Altitude | Less than 1000 meters, derating is required for more than 1000 meters |
| Humidity | Less than 95%RH, no condensation |
| Vibration resistance | 3.5m/s² at 2-9Hz, 10m/s² at 9-200Hz (IEC60721-3-3) |
| Protection Degree | IP54 |
| Pollution Level | Class 2 (dry, non-conductive dust pollution) |
| Electrical Specification | |
| Input Voltage | Single Phase/Three Phase 200-240V, Three Phase 380-440V |
| Fluctuate no more than±10%,Imbalance Rate <3% | |
| Input Frequency | 50/60Hz ± 5% |
| Output Voltage | 0V-Input Voltage |
| 10~60Hz | |
| Performance | |
| Overload Capacity | 110% rated output current for 1 minute |
| Control Method | V/F Control |
| Run Command Setting Method | Operation panel setting, analog setting, communication setting |
| Speed Setting Method | Digital setting, analog setting/pulse setting, communication setting |
| Protective function | |
| Overvoltage Stall | Bus voltage automatic control to prevent overvoltage fault |
| Automatic Current Limiting Protection | Output current is automatically limited to prevent over-current faults |
| Overload Pre-Alarm & Alarm | Overload Pre-warning and protection |
| Output Phase Loss Protection | Output phase loss automatic detection and alarm function |
| Overvoltage & Overflow Stall Control | Automatically limit current and voltage during operation to prevent frequent over-current and over-voltage tripping |
| Output Short-to-Ground Protection | Effective protection function for output short circuit to ground |
| Output Phase-to-Phase Short Circuit Protection | Output interphase short circuit effective protection function |
| Input & Output | |
| External analog power supply | +24V,load capacity 100mA |
| Analog Input | AI1:Voltage 0-10V/0-20mA |
| AI2:Voltage 0-10V/0-20mA | |
| Digital Input | DI1、DI2 |
| Digital Output | DO1 |
| Relay output | TA/TB/TC:Contact rating 250VAC/3A Or 30VDC/1A |
| MUDBUS Communication | A+、B- |
| Operation Display | |
| LED Display | 4 digit LED digital tube |
| Output frequency, output current, current pressure, set pressure and fault code etc. | |
| Indicator Light | 4 status lights |
| Environmental characteristics | |
| Working Temperature | -10-+40℃, Maximum temperature is 50°C, Air Temperature change is less than 0.5°C/min,40-50℃ Derating is required, output current derating 2% for each 1℃ |
| Storage Environment Temperature | -40-+70℃ |
| Altitude | Less than 1000 meters, derating is required for more than 1000 meters |
| Humidity | Less than 95%RH, no condensation |
| Vibration resistance | 3.5m/s² at 2-9Hz, 10m/s² at 9-200Hz (IEC60721-3-3) |
| Protection Degree | IP54 |
| Pollution Level | Class 2 (dry, non-conductive dust pollution) |