| SKU: | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Availability: | |||||||||
| Quantity: | |||||||||
| FC610: The Intelligent Brain for Modern Water Systems. The FC610 Series is a high-performance, integrated VFD specifically engineered by Janson Controls for the water pump industry. It moves beyond simple motor control to provide a complete water management solution for small to medium power applications. Stable Pressure, Zero Hassle: With its advanced Built-in PID, the FC610 maintains precise constant pressure, eliminating annoying water pressure fluctuations in buildings and factories. Intelligent Multi-Pump Staging: Manage up to 5 pumps simultaneously. The FC610 intelligently balances the load and rotates pump usage to ensure equal wear and tear, significantly extending your equipment's lifespan. Ultimate Pump Protection: Features specialized safety logic, including Dry-Run Protection and Pipe-Burst Detection, preventing catastrophic pump failures and costly repairs. Energy-Saving Sleep Mode: Automatically enters low-power mode during zero-demand periods, cutting energy costs by up to 30%–50% for residential and commercial users. | |||||||||
FC610
Janson Controls
1.Intelligent Control for Water Stability
Advanced Constant Pressure Logic: Real-time feedback from pressure sensors ensures the system reacts instantly to demand changes.
Multi-Pump Master/Slave Mode: Supports intelligent staging of up to 5 pumps (VFD + fixed speed combination). Includes automatic rotation to prevent pump seizure from long-term inactivity.
2.Proactive Safety & Durability
Specialized Pump Safeguards: Integrated protection against dry-running, high/low pressure, pipe leakage, and motor overheating.
Grid & Environment Resilience: Tolerates ±15% voltage fluctuations and features a reinforced enclosure to withstand the humidity and heat of tropical pump rooms.
3.Eco-Friendly & Cost-Effective
Smart Sleep/Wake-up: The drive "sleeps" when demand stops and "wakes up" instantly when pressure drops, drastically reducing electricity bills.
Simplified Engineering: Built-in macros for pump applications mean you don't need to be a VFD expert to get the system running perfectly.
4.Connectivity & Remote Monitoring
Dual RS485 Ports: Standard Modbus-RTU communication for easy integration with Building Management Systems (BMS) or remote IoT monitoring apps.
Flexible Interfaces: Easily connect pressure transducers, float switches, and remote emergency stops for a fully automated station.
1.Intelligent Control for Water Stability
Advanced Constant Pressure Logic: Real-time feedback from pressure sensors ensures the system reacts instantly to demand changes.
Multi-Pump Master/Slave Mode: Supports intelligent staging of up to 5 pumps (VFD + fixed speed combination). Includes automatic rotation to prevent pump seizure from long-term inactivity.
2.Proactive Safety & Durability
Specialized Pump Safeguards: Integrated protection against dry-running, high/low pressure, pipe leakage, and motor overheating.
Grid & Environment Resilience: Tolerates ±15% voltage fluctuations and features a reinforced enclosure to withstand the humidity and heat of tropical pump rooms.
3.Eco-Friendly & Cost-Effective
Smart Sleep/Wake-up: The drive "sleeps" when demand stops and "wakes up" instantly when pressure drops, drastically reducing electricity bills.
Simplified Engineering: Built-in macros for pump applications mean you don't need to be a VFD expert to get the system running perfectly.
4.Connectivity & Remote Monitoring
Dual RS485 Ports: Standard Modbus-RTU communication for easy integration with Building Management Systems (BMS) or remote IoT monitoring apps.
Flexible Interfaces: Easily connect pressure transducers, float switches, and remote emergency stops for a fully automated station.
| Item No. | Adaptable Motor (kW) | Input Current (A) | Output Current (A) | Rate Capacity (kVA) | W (mm) | H (mm) | D (mm) | W1 (mm) | H1 (mm) | GW (kg) |
| 3 Phase Input and 3 Phase Output 380V (-15%~+15% Tolerance) | ||||||||||
| FC610-4T-2.2P | 2.2 | 5.8 | 5.1 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-4.0P | 4 | 10 | 8.6 | 5.9 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-5.5P | 5.5 | 14.6 | 12.5 | 8.6 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-7.5P | 7.5 | 20.5 | 17.5 | 12 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-11P | 11 | 28 | 25 | 16 | 200 | 235 | 146 | 129 | 225 | 4 |
| 1 Phase Input and 3 Phase Output 220V (-15%~+15% Tolerance) | ||||||||||
| FC610-2S-0.75P | 0.75 | 8.2 | 4 | 1.5 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-1.5P | 1.5 | 14 | 7 | 3 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-2.2P | 2.2 | 23 | 9.6 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| Item No. | Adaptable Motor (kW) | Input Current (A) | Output Current (A) | Rate Capacity (kVA) | W (mm) | H (mm) | D (mm) | W1 (mm) | H1 (mm) | GW (kg) |
| 3 Phase Input and 3 Phase Output 380V (-15%~+15% Tolerance) | ||||||||||
| FC610-4T-2.2P | 2.2 | 5.8 | 5.1 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-4.0P | 4 | 10 | 8.6 | 5.9 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-4T-5.5P | 5.5 | 14.6 | 12.5 | 8.6 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-7.5P | 7.5 | 20.5 | 17.5 | 12 | 200 | 235 | 146 | 129 | 225 | 3.85 |
| FC610-4T-11P | 11 | 28 | 25 | 16 | 200 | 235 | 146 | 129 | 225 | 4 |
| 1 Phase Input and 3 Phase Output 220V (-15%~+15% Tolerance) | ||||||||||
| FC610-2S-0.75P | 0.75 | 8.2 | 4 | 1.5 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-1.5P | 1.5 | 14 | 7 | 3 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| FC610-2S-2.2P | 2.2 | 23 | 9.6 | 4 | 126 | 173 | 136 | 101 | 158 | 2.48 |
| Electrical Specification | |
| Input Voltage | Single Phase/Three Phase 200-240V, Three Phase 380-440V |
| Fluctuate no more than±10%,Imbalance Rate <3% | |
| Input Frequency | 50/60Hz ± 5% |
| Output Voltage | 0V-Input Voltage |
| 10~60Hz | |
| Performance | |
| Overload Capacity | 110% rated output current for 1 minute |
| Control Method | V/F Control |
| Run Command Setting Method | Operation panel setting, analog setting, communication setting |
| Speed Setting Method | Digital setting, analog setting/pulse setting, communication setting |
| Protective function | |
| Overvoltage Stall | Bus voltage automatic control to prevent overvoltage fault |
| Automatic Current Limiting Protection | Output current is automatically limited to prevent over-current faults |
| Overload Pre-Alarm & Alarm | Overload Pre-warning and protection |
| Output Phase Loss Protection | Output phase loss automatic detection and alarm function |
| Overvoltage & Overflow Stall Control | Automatically limit current and voltage during operation to prevent frequent over-current and over-voltage tripping |
| Output Short-to-Ground Protection | Effective protection function for output short circuit to ground |
| Output Phase-to-Phase Short Circuit Protection | Output interphase short circuit effective protection function |
| Input & Output | |
| External analog power supply | +24V,load capacity 100mA |
| Analog Input | AI1:Voltage 0-10V/0-20mA |
| AI2:Voltage 0-10V/0-20mA | |
| Digital Input | DI1、DI2 |
| Digital Output | DO1 |
| Relay output | TA/TB/TC:Contact rating 250VAC/3A Or 30VDC/1A |
| MUDBUS Communication | A+、B- |
| Operation Display | |
| LED Display | 4 digit LED digital tube |
| Output frequency, output current, current pressure, set pressure and fault code etc. | |
| Indicator Light | 4 status lights |
| Environmental characteristics | |
| Working Temperature | -10-+40℃, Maximum temperature is 50°C, Air Temperature change is less than 0.5°C/min,40-50℃ Derating is required, output current derating 2% for each 1℃ |
| Storage Environment Temperature | -40-+70℃ |
| Altitude | Less than 1000 meters, derating is required for more than 1000 meters |
| Humidity | Less than 95%RH, no condensation |
| Vibration resistance | 3.5m/s² at 2-9Hz, 10m/s² at 9-200Hz (IEC60721-3-3) |
| Protection Degree | IP54 |
| Pollution Level | Class 2 (dry, non-conductive dust pollution) |
| Electrical Specification | |
| Input Voltage | Single Phase/Three Phase 200-240V, Three Phase 380-440V |
| Fluctuate no more than±10%,Imbalance Rate <3% | |
| Input Frequency | 50/60Hz ± 5% |
| Output Voltage | 0V-Input Voltage |
| 10~60Hz | |
| Performance | |
| Overload Capacity | 110% rated output current for 1 minute |
| Control Method | V/F Control |
| Run Command Setting Method | Operation panel setting, analog setting, communication setting |
| Speed Setting Method | Digital setting, analog setting/pulse setting, communication setting |
| Protective function | |
| Overvoltage Stall | Bus voltage automatic control to prevent overvoltage fault |
| Automatic Current Limiting Protection | Output current is automatically limited to prevent over-current faults |
| Overload Pre-Alarm & Alarm | Overload Pre-warning and protection |
| Output Phase Loss Protection | Output phase loss automatic detection and alarm function |
| Overvoltage & Overflow Stall Control | Automatically limit current and voltage during operation to prevent frequent over-current and over-voltage tripping |
| Output Short-to-Ground Protection | Effective protection function for output short circuit to ground |
| Output Phase-to-Phase Short Circuit Protection | Output interphase short circuit effective protection function |
| Input & Output | |
| External analog power supply | +24V,load capacity 100mA |
| Analog Input | AI1:Voltage 0-10V/0-20mA |
| AI2:Voltage 0-10V/0-20mA | |
| Digital Input | DI1、DI2 |
| Digital Output | DO1 |
| Relay output | TA/TB/TC:Contact rating 250VAC/3A Or 30VDC/1A |
| MUDBUS Communication | A+、B- |
| Operation Display | |
| LED Display | 4 digit LED digital tube |
| Output frequency, output current, current pressure, set pressure and fault code etc. | |
| Indicator Light | 4 status lights |
| Environmental characteristics | |
| Working Temperature | -10-+40℃, Maximum temperature is 50°C, Air Temperature change is less than 0.5°C/min,40-50℃ Derating is required, output current derating 2% for each 1℃ |
| Storage Environment Temperature | -40-+70℃ |
| Altitude | Less than 1000 meters, derating is required for more than 1000 meters |
| Humidity | Less than 95%RH, no condensation |
| Vibration resistance | 3.5m/s² at 2-9Hz, 10m/s² at 9-200Hz (IEC60721-3-3) |
| Protection Degree | IP54 |
| Pollution Level | Class 2 (dry, non-conductive dust pollution) |
content is empty!